Site home page Get alerts when Linktionary is updated Book updates and addendums Get info about the Encyclopedia of Networking and Telecommunicatons, 3rd edition (2001) Download the electronic version of the Encyclopedia of Networking, 2nd edition (1996). It's free! Contribute to this site Electronic licensing info
|
TIA/EIA Structured Cabling Standards Related Entries Web Links New/Updated Information Note: Many topics at this site are reduced versions of the text in "The Encyclopedia of Networking and Telecommunications." Search results will not be as extensive as a search of the book's CD-ROM. In the mid-1980s, the TIA (Telecommunications Industry Association) and the EIA (Electronic Industries Association) began developing methods for cabling buildings, with the intent of developing a uniform wiring system that would support multivendor products and environments. In 1991, the TIA/EIA released the TIA/EIA 568 Commercial Building Telecommunication Cabling standard. Note that the ISO/IEC-11801 Generic Customer Premises Cabling standard is an international cabling standard that is based on the ANSI/TIA/EIA-568 cabling standard. The TIA/EIA structured cabling standards define how to design, build, and manage a cabling system that is structured, meaning that the system is designed in blocks that have very specific performance characteristics. The blocks are integrated in a hierarchical manner to create a unified communication system. For example, workgroup LANs represent a block with lower-performance requirements than the backbone network block, which requires high-performance fiber-optic cable in most cases. The standard defines the use of fiber-optic cable (single and multimode), STP (shielded twisted pair) cable, and UTP (unshielded twisted pair) cable. The initial TIA/EIA 568 document was followed by several updates and addendums as outlined below. A major standard update was released in 2000 that incorporates previous changes.
The current trend is to evolve the standards to support high-speed networking such as Gigabit Ethernet and define advanced cable types and connectors such as four-pair Category 6 and Category 7 cable. Category 6 is rated for channel performance up to 200 MHz, while Category 7 is rated up to 600 MHz. See "Cable and Wiring" for more information about cable types. The remainder of this section discusses the TIA/EIA-568 standard in general, rather than any specific release. According to TIA/EIA 568 documents, the wiring standard is designed to provide the following features and functions:
The layout of a TIA/EIA 568-A structured cable system is illustrated in Figure T-8. The hierarchical structure is apparent in the multifloor office building. A vertical backbone cable runs from the central hub/switch in the main equipment room to a hub/switch in the telecommunication closet on each floor. Work areas are then individually cabled to the equipment in the telecommunication closet. The logical hierarchy is illustrated in Figure T-9. Figure T-8 (see book, page 1248) Figure T-9 (see book, page 1249) The TIA standard defines the parameters for each part of the cabling system, which includes work area wiring, horizontal wiring, telecommunication closets, equipment rooms and cross- connects, backbone (vertical) wiring, and entrance facilities. Each of these is described next. Additional details, specifications, and illustrations are available at the Siemon's Web site listed on the related entries page. Work Area The work area wiring subsystem consists of the communication outlets (wallboxes and faceplates), wiring, and connectors needed to connect the work area equipment (computers, printers, and so on) via the horizontal wiring subsystem to the telecommunication closet. The standard requires that two outlets be provided at each wall plate-one for voice and one for data. Horizontal Wiring The horizontal wiring system runs from each workstation outlet to the telecommunication closet. The maximum horizontal distance from the telecommunication closet to the communication outlets is 90 meters (295 feet) independent of media type. An additional 6 meters (20 feet) is allowed for patch cables at the telecommunication closet and at the workstation, but the combined length cannot exceed 10 meters (33 feet). As mentioned earlier, the work area must provide two outlets. The horizontal cable should be four-pair 100-ohm UTP cable (the latest standards specify Category 5E), two-fiber 62.5/125-mm fiber-optic cable, or multimode 50/125-mm multimode fiber-optic cable. Coaxial cable is no longer recommended. Telecommunication Closet The telecommunication closet contains the connection equipment for workstations in the immediate area and a cross-connection to an equipment room. The telecommunication closet is a general facility that can provide horizontal wiring connections, as well as entrance facility connections. There is no limit on the number of telecommunication closets allowed. Some floors in multistory office buildings may have multiple telecommunication closets, depending on the floor plan. These may be connected to an equipment room on the same floor. Equiptment Rooms and Main Cross-Connects An equipment room provides a termination point for backbone cabling that is connected to one or more telecommunication closets. It may also be the main cross-connection point for the entire facility. In a campus environment, each building may have its own equipment room, to which telecommunication closet equipment is connected, and the equipment in this room may then be connected to a central campus facility that provides the main cross-connect for the entire campus. Backbone Wiring The backbone wiring runs up through the floors of the building (risers) or across a campus and provides the interconnection for equipment rooms and telecommunication closets. The distance limitations of this cabling depend on the type of cable and facilities it connects. Refer to Figure T-11 and the following table. Note that UTP is limited to 90 meters.
Entrance Facilities The entrance facility contains the telecommunication service entrance to the building. This facility may also contain campus-wide backbone connections. It also contains the network demarcation point, which is the interconnection to the local exchange carrier's telecommunication facilities. The demarcation point is typically 12 inches from where the carrier's facilities enter the building, but the carrier may designate otherwise. Copyright (c) 2001 Tom Sheldon and Big Sur Multimedia. |